Feature:
●200 amps continuous carry,product miniaturization and lightweight
●Max. Load current capacity:8000A
●2000 amps interrupte under extreme condition
●Hermetically sealed with hydrogen gas,thearcis not exposed.Beableto usein explosive &harsh environments without oxidation or contamination of contacts
●There is no polarityrequirement for load wiring and no polarity requirement for coil drive
| ltem | Specification | |
| Mechanical endurance | 2×105 cycle | |
| Insulation resistance | 1000MΩ(1000VDC) | |
|
Dielectric strength |
Between open contacts | 4000VAC 1min. 1mA |
| Between contaci and coil | 4000VAC 1min. 1mA | |
| Operation time(at rated coil voltage) | ≤30ms | |
| Release time(at rated coil voltage) | ≤10ms | |
| Shock resistance | Functional |
Closed state:490m/s2(50G) Disconnected state:98m/s2(10G) |
| Destructive | 490m/s2(50G) | |
| Vibration resistance | 10Hz~500Hz 49m/s2(5G) | |
| Ambient temperature | -40℃~+85℃ | |
| Ambient humidity | 5%~85% RH | |
| Weight | 325g | |
| External dimension | 81x 39 x 70 | |